SEW變頻器MOVITRAC-07系列故障代碼詳表

發布時間:2019-08-02 15:40:24來源:

故障代碼 故障現象/類型 故障原因 解決對策
01 Over-current • Short circuit on output • Output switching • Motor too large • Defective output stage • Ramp limit (P138) switched off • Rectify the short circuit • Only switch when output stage inhibited • Connect a smaller motor • Call SEW Service for advice if the fault still cannot be reset • Ramp limit (P138 = YES)
03 Ground fault • Ground fault on motor • Ground fault on inverter • Ground fault in the motor lead • Over-current (see F-01) • Replace the motor • Replace the MOVITRAC® 07 • Rectify the ground fault • See F-01
04 Brake chopper • Regenerative power excessive • Braking resistor circuit interrupted • Short circuit in braking resistor circuit • Excessively high braking resistance • Brake chopper defective • Ground fault • Extend deceleration ramps • Check connecting harness for braking resistor • Rectify the short circuit • Check technical data of braking resistor • Replace the MOVITRAC® 07 • Rectify the ground fault
06 Supply system phase failure (only with three-phase inverter) Phase fault Check supply system lead
07 DC-link overvoltage • DC link voltage too high • Ground fault • Extend deceleration ramps • Check connecting harness for braking resistor • Check technical data of braking resistor • Rectify the ground fault
08 Speed monitoring Current controller is operating at the setting limit due to: • mechanical overload • phase failure in supply system • phase failure in motor • Reduce load • Increase delay time setting P501 • Check current limitation • Extend deceleration ramps • Check supply system phases • Check motor feeder and motor Maximum speed for VFC operating mode exceeded • Reduce load • Increase delay time setting P501 • Check current limitation • Extend deceleration ramps • Check supply system phases • Check motor feeder and motor Maximum speed for VFC operating mode exceeded • Reduce maximum speed
10 ILLOP • Incorrect command during running of program • Incorrect conditions during running of program • Function not in inverter / not implemented • Check program • Check program structure • Use another function
11 Overtemperature Thermal overload of inverter • Reduce load and/or ensure adequate cooling • If the braking resistor is integrated in the heat sink: Mount the braking resistor externally
17-24 System fault Inverter electronics disrupted, possibly due to effect of EMC Check ground connections and shields; improve them if necessary. Contact SEW Service for advice if this reoccurs.
25 EEPROM Fault when accessing EEPROM Call up default setting, perform reset and set parameters again. Contact SEW Service for advice if this reoccurs.
26 External terminal Read in external fault signal via programmable input Eliminate specific cause of fault; reprogram terminal if appropriate.
31 TF sensor • Motor too hot, TF sensor has tripped • TF sensor of motor not connected or not connected properly • Connection of MOVITRAC® 07 and TF interrupted on motor • Let motor cool down and reset fault • Check connections/links between MOVITRAC® 07 and TF
32 Index overrun Basic programming rules violated causing internal stack overflow Check and correct user program
34 Ramp timeout The inverter signals F34 if you revoke the enable and the drive exceeds the rapid stop ramp time t13 by a certain time. Extend the rapid stop ramp time
37 Watchdog timer Fault in system software sequence Check ground connections and shields; improve them if necessary. Contact SEW Service for advice if this reoccurs.
38 System software System fault Check ground connections and shields; improve them if necessary. Contact SEW Service for advice if this reoccurs.
43 RS-485 timeout Communication between inverter and PC interrupted Check connection between inverter and PC.
44 Unit utilization Unit utilization (Ixt value) excessive • Reduce power output • Extend ramps • If these points are not possible: Use a larger inverter
45 Initialization Error during initialization Contact SEW Service for advice.
47 System bus timeout Fault during communication via system bus Check system bus connection.

故障代碼 故障現象/類型 故障原因 解決對策
77 Control word An external control has attempted to set an invalid automatic mode • Check serial connection to external control • Check write values of external control
81 Start condition Only in "VFC hoist" operating mode: The inverter could not inject the required amount of current into the motor during the pre-magnetization time: • Motor rated power too small in relation to inverter rated power • Motor cable cross section too small • Check connection between inverter and motor • Check startup data and repeat startup if necessary
82 Output open Only in "VFC hoist" operating mode: • Two or all output phases interrupted • Motor rated power too small in relation to inverter rated power Check connection between inverter and PC.
94 EEPROM checksum EEPROM defective Contact SEW Service for advice.
97 Copy fault • Parameter module disconnected during copying process • Switching off/on during copying process Prior to acknowledging the fault: • Load the factory setting or the complete data record from the parameter module
、、、、、、、長治變頻器維修、、、、信陽變頻器維修、、、,河南鄭州變頻器專業銷售維修中心,技術精湛,質量可靠,價格比較低,信譽保證!變頻器維修電話:15515598858 0371-56700815
用手機看
SEW變頻器MOVITRAC-07系列故障代碼詳表

拍下二維碼,信息隨身看

試試用手機掃一掃,
在你手機上繼續觀看此頁面。

主站蜘蛛池模板: 9久久免费国产精品特黄 | 91亚洲在线 | 国产国产精品四虎视频精品 | 四虎免费网址 | 牛牛影视在线观看片免费 | 四虎永久网址在线观看 | 久久久亚洲欧洲国产 | 香蕉狠狠干 | 午夜视频福利在线观看 | 四虎影视在线影院在线观看观看 | 天天干天天综合 | 一级片视频网站 | 人人看97| 伊人伊人网 | 国模无水印一区二区三区 | 福利在线国产 | 老子影院无码午夜伦不卡 | 国产日韩欧美精品一区二区三区 | 亚洲欧美日韩高清一区二区三区 | 午夜精品久久久久久99热 | 性欧美网站 | 色片在线免费观看 | 亚洲欧洲一二三区机械有限公司 | 精品伦理 | 久久最新精品 | 伊人不卡久久大香线蕉综合影院 | 四虎影视在线观看2413 | 亚洲一区二区三区四区热压胶 | 全亚洲最大的免费私人影剧院 | 四虎在线精品观看免费 | 成年女人在线观看 | 欧洲黄色网 | 日本乱中文字幕系列在线观看 | 国产高清国内精品福利99久久 | 伊人333| 国产香蕉75在线播放 | 97精品国产手机 | 国内揄拍国内精品久久 | 久久天堂网 | 欧美与黑人午夜性猛交久久久 | 久久久久久青草大香综合精品 |